Find the smallest copper or aluminum wire for a load, or look up any AWG size.

Before you rely on this result. This is a planning estimate from NEC Table 310.16 under its stated conditions, not a design or a code approval. An electrician and your local inspector decide what is installed. Sources used on this page.

How it's worked out

Sizing a wire is a two-part test. First the wire must carry the current without overheating, which NEC Table 310.16 sets as its ampacity, the current it can carry all the time without passing its temperature rating. Then, on a long run, it must not lose too much voltage. The size you need is whichever of the two is larger.

Ampacity. The table has columns for insulation rated 60, 75 and 90 °C, and it holds for no more than three current-carrying conductors together in a 30 °C room. The tool reads the 60 or 75 °C column for copper and aluminum. NM cable, the usual house wiring, may not exceed its 60 °C ampacity under 334.80, and 110.14(C) holds a wire to the rating of the terminals it lands on, so the lower of the two sets the column.

Small sizes. Section 240.4(D) caps the breaker on 14, 12 and 10 AWG copper at 15, 20 and 30 A, below their table ratings, and on 12 and 10 AWG aluminum at 15 and 25 A. The tool picks the first size whose cap covers the load.

Size itself. The gauge is a fixed series. NBS Handbook 100 defines 4/0 as 0.4600 in and 36 AWG as 0.0050 in, with 39 equal steps between them, so each step is the 39th root of 92 larger in diameter.

d\displaystyle d=0.005×9236−n39 in\displaystyle {}= 0.005 \times 92^{\frac{36 - n}{39}}\ \text{in}

Here n is the gauge number, with 1/0 as 0, 2/0 as −1 and 4/0 as −3. The area in circular mils is the diameter in thousandths of an inch, squared. Resistance per 1,000 ft is 12.9 × 1,000 over that area for copper at 75 °C, or 21.2 × 1,000 for aluminum.

Worked examples

Marco wires a 30 A water heater

A 30 A load on copper at 75 °C needs 10 AWG. The table rates it at 35 A, and 240.4(D) lets it sit on a breaker of up to 30 A, which just covers the load.

At 240 V, 10 AWG can run about 97 ft before the drop reaches 3%. Marco's heater is 100 ft away, so the drop check moves him up to 8 AWG.

Open this example in the tool

Ana runs a 20 A circuit 150 ft

Ana's 16 A load is well inside what 12 AWG copper may carry. Over 150 ft at 120 V, though, keeping the drop under 3% takes 6 AWG.

So the run sets the size, not the current: 6 AWG, with 13.3 mm² of copper against 3.31 mm² for 12 AWG.

Open this example in the tool

Sam feeds a 100 A subpanel in aluminum

For 100 A at 75 °C, aluminum needs 1 AWG, where copper would need 3 AWG. The 80 ft run alone would allow 3 AWG, so ampacity sets the size here.

A feeder that supplies the whole of a one-family dwelling may use the smaller sizes of 310.12, which this tool does not apply. Aluminum also needs connectors rated for it.

Open this example in the tool

Reading your result

The answer is a minimum. A larger wire is always allowed and drops less voltage. The breaker limit in the answer is the most the wire may be protected at; the load sets the breaker you actually pick.

The column matters. At 60 °C a 50 A load needs 6 AWG copper; at 75 °C it needs 8 AWG. Check what your cable and both ends of the run are rated for before reading the 75 °C column.

Area is what you pay for. Every three gauge numbers about doubles the area: 2.005 times, by the AWG definition. 14, 12 and 10 AWG are 2.08 mm², 3.31 mm² and 5.26 mm².

This is a planning estimate. It does not apply correction factors for hot spaces or bundled cables, the 125% rule for continuous loads, or the special rules for motors and air conditioners. An electrician and your local inspector decide what is installed.

Common mistakes

  • Reading the 75 °C column for NM cable. House cable is held to its 60 °C ampacity, so use that column for it.
  • Sizing to the table and forgetting the breaker cap. 12 AWG copper is rated 25 A in the 75 °C column, but it may not go on a breaker larger than 20 A.
  • Swapping copper for aluminum at the same size. Aluminum carries less: 20 A needs 10 AWG aluminum against 12 AWG copper.
  • Ignoring the run length. A size that carries the current can still lose too much voltage over a long run. Turn the drop check on for anything past a few dozen feet.

Questions people ask

At 75 °C, 10 AWG copper is the smallest, because 240.4(D) lets it sit on a 30 A breaker. Over a long run it may need to be bigger: on 240 V it reaches 3% drop at about 97 ft, and 8 AWG keeps you under it out to about 154 ft.