Voltage Drop
calculator.
See how many volts a cable run loses, and the smallest wire size that keeps it in check.
- Percent drop
- 5.27%
- At the load
- 113.7 V
- Smallest for 3%
- 8 AWG
This run loses 5.27%, over your 3% limit. 8 AWG brings it to 2.08%, or 12 AWG would do it on a run of 56.9 ft or less.
Drop along the run
Drag the point to change the lengthPercent drop rises in a straight line with the length. On 12 AWG copper this run of 100 ft loses 5.27%, and the 3% limit comes at 56.9 ft; 10 AWG would lose 3.31% here.
Working
- 1K-factor formula, out and backVD =2 × K × I × LCM
- 2Put in K for copper and the area of 12 AWGVD =2 × 12.9 × 16 × 1006,530= 6.322 V
- 3Share of the source voltage6.322120× 100 = 5.27%
- 4Check: the voltage at the load plus the drop gives the source back113.7 + 6.322 = 120 V
Every size on this run
| Size | Drop (V) | Drop (%) | 75 °C ampacity |
|---|---|---|---|
| 18 AWGnot listed | 25.4 | 21.2% | – |
| 16 AWGnot listed | 16 | 13.3% | – |
| 14 AWG20 A at 75 °C | 10.1 | 8.38% | 20 A |
| 12 AWG (yours)25 A at 75 °C | 6.32 | 5.27% | 25 A |
| 10 AWG35 A at 75 °C | 3.98 | 3.31% | 35 A |
| 8 AWG50 A at 75 °C | 2.5 | 2.08% | 50 A |
| 6 AWG65 A at 75 °C | 1.57 | 1.31% | 65 A |
| 4 AWG85 A at 75 °C | 0.989 | 0.824% | 85 A |
Your drop limit
The 3% and 5% figures come from informational notes in NFPA 70, which say conductors sized to them give reasonable efficiency of operation. A note is guidance, not a rule you can be cited for, and this estimate is not a code approval.
How far this wire can go
- Longest run on 12 AWG at 3%
- 56.9 ft
- Smallest size for 100 ft
- 8 AWG
- Its drop on this run
- 2.08%
Both use the same current, voltage and single-phase or DC formula as the answer.
How it's worked out
A wire is a long, thin resistor. Current flowing through it turns some of the supply into heat, so the load gets a little less than the panel sends. The usual way to estimate that loss is the K-factor method, which IAEI describes from the resistance values in NEC Chapter 9, Table 8.
Here I is the load current in amps, L is the one-way length in feet, and CM is the wire's area in circular mils. A circular mil is the area of a circle one thousandth of an inch across, so a wire's area in circular mils is its diameter in mils, squared. K is the resistance of a conductor one circular mil in area and one foot long: about 12.9 ohms for copper and 21.2 for aluminum, taken at a 75 °C operating temperature.
The 2 counts the trip out and the trip back. In a balanced three-phase circuit the return currents cancel, and the drop between lines uses 1.732, the square root of 3, in its place.
The percent drop is the drop divided by the source voltage. The wire areas come from the American Wire Gauge itself: NBS Handbook 100 defines 4/0 as 0.4600 in and 36 AWG as 0.0050 in, with 38 sizes spaced evenly between them, so each step up is about 26% more copper.
Worked examples
Dana runs a 120 V circuit to her shed
Dana plans 16 A on a 20 A circuit, 100 ft from the panel, in 12 AWG copper. The wire drops 6.32 V, which is 5.27% of 120 V, so her saw sees 114 V.
That is well past the 3% planning figure. 8 AWG brings the same run down to 2.08%. Staying with 12 AWG would mean a run of no more than 57 ft.
Leo wires a 12 V solar panel
Leo's panel pushes 20 A down 30 ft of 10 AWG to the charge controller. The drop is only 1.49 V, but on a 12 V system that is 12.4% of everything the panel makes.
To get under 3% he needs 3 AWG, thick cable for a short run. Wiring the panels for 24 V at 10 A would let 8 AWG do the job, because the current halves and each lost volt is a smaller share.
Priya checks a 480 V motor feeder
Priya's motor draws 50 A on a three-phase feeder 200 ft long in 6 AWG copper. The drop is 8.51 V, just 1.77%. The same size could run about 338 ft before reaching 3%.
The cable still turns about 737 W into heat while the motor runs. Had she used the single-phase factor of 2 by mistake, she would have read 9.83 V, higher than the real drop.
Reading your result
The percent is the number to compare. A 6 V drop is a lot on 120 V and very little on 480 V. The answer gives both, and the voltage left at the load.
Where 3% and 5% come from. NFPA 70 has informational notes for feeders (215.2) and branch circuits (210.19). The feeder note, in NFPA's working text for the 2026 edition, says conductors sized to keep the drop under 3% at the farthest outlet, and under 5% for feeder and branch circuit together, give reasonable efficiency of operation. IAEI points out that informational notes are not mandatory rules. So this tool calls a result inside or over your limit, never compliant or not.
What changes it. The drop rises in step with current and length, and falls as the wire gets bigger. Three gauge numbers up doubles the area and halves the drop. Raising the voltage for the same power cuts the current, and the percent falls with the square of that change.
What this estimate leaves out. It uses resistance at 75 °C and ignores the extra reactance that large AC cables have, so it reads a little low on big feeders. It is a planning figure, not a design or an inspection.
Common mistakes
- Entering the round-trip length. The formula already doubles it. Typing 200 ft for Dana's 100 ft run would show 10.5% instead of 5.27%.
- Using the breaker size as the load. Use the current the load really draws. The breaker rating gives a worst case, which can be worth a look on a circuit that might grow.
- Spending the whole 5% on the branch circuit. The 5% figure covers the feeder and the branch circuit together, so a long feeder leaves less for the circuit after it.
- Sizing for drop and forgetting ampacity. A size that passes the drop check can still be too small for the current. Wire must meet both, and the tool warns when the current passes the 75 °C rating in NEC Table 310.16.
Questions people ask
Sources
- IAEI Magazine, Voltage drop formulas
- NFPA 70, 2026 cycle, CMP-10 first-draft working text, 215.2 Informational Note No. 2
- NFPA 70, 2026 cycle, CMP-6 first-draft working text, Table 310.16
- NBS Handbook 100, Copper Wire Tables (1966)
- EC&M, How to use Chapter 9 in your next design
- NIST Guide to the SI, Appendix B.8