Power Factor
calculator.
See how much of the current in an AC load does useful work, and what fixes the rest.
- Real power P
- 1.84 kW
- Reactive power Q
- 1.38 kvar
- Apparent power S
- 2.3 kVA
At 0.8 the wiring carries 25% more current than the same work needs at unity. Many utilities charge a fee below 0.95; 775 var of capacitors would reach it.
The power triangle
Slide the power factor to reshape itReal power 1.84 kW along the bottom, reactive power 1.38 kvar up the side and apparent power 2.3 kVA on the long side, at 36.9°.
Working
- 1Apparent power: voltage times currentS = 230 × 10 = 2.3 kVA
- 2Real power: apparent power times the power factorP = 2.3 kVA × 0.8 = 1.84 kW
- 3Reactive power: the third side of the triangleQ = √(S² − P²) = 1.38 kvar, at a phase angle of 36.87°
- 4Check: real power over apparent power gives back the power factor1.84 kW ÷ 2.3 kVA = 0.8 ✓
What each target would take
| Target | Capacitors | µF | S after | Current |
|---|---|---|---|---|
| 0.9 | 489 var24.5 µF | 24.5 | 2.04 kVA11.1% less current | 11.1% less |
| 0.92 | 596 var29.9 µF | 29.9 | 2 kVA13% less current | 13% less |
| 0.95 | 775 var38.9 µF | 38.9 | 1.94 kVA15.8% less current | 15.8% less |
| 0.98 | 1.01 kvar50.5 µF | 50.5 | 1.88 kVA18.4% less current | 18.4% less |
| 1 | 1.38 kvar69.2 µF | 69.2 | 1.84 kVA20% less current | 20% less |
Same real power on every row, at 230 V and 60 Hz. The last few hundredths cost the most kvar for the least current saved.
Low power factor fees
| Power factor | Reading |
|---|---|
| 0.95 or more | No low power factor fee on many tariffs |
| Below 0.95 | Many utilities add a fee |
From the US Department of Energy fact sheet on power factor. Your tariff sets the real rule. This load: 0.8, below the line.
How it's worked out
In an AC circuit with motors or transformers, the current runs out of step with the voltage. Only part of what the wiring carries does work. Power factor is the ratio of real power to apparent power, and it equals the cosine of the phase angle between voltage and current.
Real power , in watts, does the work. Reactive power , in var, builds the magnetic field and flows back and forth. Apparent power , in volt-amperes (VA), is what the supply and cables must carry. The three form a right triangle.
For a single-phase load, is the voltage times the current. For a balanced three-phase load, use the line-to-line voltage and the line current, with a factor of \(\sqrt{3}\).
Capacitors supply reactive power on the spot, so less of it travels from the supply. To raise the power factor from to with the same real power, the capacitors must cancel the difference in .
Here is the supply frequency and the voltage across the capacitor. In a three-phase bank wired in delta, each of the three capacitors takes a third of with the line voltage across it.
Worked examples
A 230 V motor drawing 10 A at a power factor of 0.8
The supply carries 2,300 VA, but only 1,840 W does work, and 1,380 var swaps back and forth. The phase angle is 36.87°.
At a power factor of 1 the same 1,840 W would need only 8 A. The extra amps still heat the cable, even though they do no work.
Reading a meter that shows 800 W and 1,000 VA
Real over apparent gives a power factor of 0.8. The third side of the triangle is 600 var, at a phase angle of 36.87°.
You need both readings. A meter that shows only watts cannot tell you the power factor, and volts times amps alone gives only the apparent power.
Correcting a 100 kW plant from 0.70 to 0.95
At 0.70 the plant draws 142.9 kVA. Reaching 0.95 takes 69.15 kvar of capacitors, which on a 480 V, 60 Hz delta bank is 265.4 µF per phase. The line current falls from 171.8 to 126.6 A, 26.3% less.
Going on to 0.98 needs 81.7 kvar, and all the way to 1.00 needs 102 kvar, for a current cut of 28.6% and 30%. Each step closer to 1 buys less current for more capacitors.
Reading your result
A power factor runs from 0 to 1. At 1, voltage and current are in step and every amp does work, as in a heater. Motors, transformers and high-intensity discharge lighting pull it down, because their magnetizing current adds reactive power.
Why it costs money. Low power factor means more current for the same work. That means more heating in cables and less spare capacity. The DOE fact sheet says many utilities charge an additional fee below 0.95. Check your own tariff for the line it uses.
Light loads read worse. A motor running far below its rating has a lower power factor than its nameplate says. The DOE sheet lists cutting idling and lightly loaded motors as one of the fixes.
Inductors and capacitors use no real power. On average they take none, so adding capacitors changes the current and the apparent power, but not the watts the load uses.
Common mistakes
Using phase voltage in the three-phase formula. needs the line-to-line voltage, such as 480 V, not the 277 V from line to neutral.
Sizing capacitors on kVA instead of kW. The kvar formula starts from real power. Use the watts the load draws, not its apparent power.
Expecting capacitors to cut the watts. They lower the current and the kVA. The motor still needs the same real power, so a bill based on kWh alone barely moves.
Ordering the µF without the connection. The same kvar needs a different capacitance in a delta bank, a star bank or a single-phase unit, because the voltage across each capacitor differs.
Questions people ask
Sources
- US Department of Energy, Motor Challenge fact sheet: Reducing Power Factor Cost (DOE/GO-10096-286)
- OpenStax, University Physics Volume 2, Section 15.4: Power in an AC Circuit
- University of Utah ECE 3600, 3-Phase Power notes (A. Stolp)
- NIST Technical Note 1654: Regarding Electric Energy Savings, Power Factors, and Carbon Footprints (2009)