ScienceEngineering

Power Factor
calculator.

See how much of the current in an AC load does useful work, and what fixes the rest.

Before you rely on this result. Capacitor banks are connected to live mains. Have a qualified electrician choose, protect and install them. Sources used on this page.

How it's worked out

In an AC circuit with motors or transformers, the current runs out of step with the voltage. Only part of what the wiring carries does work. Power factor is the ratio of real power to apparent power, and it equals the cosine of the phase angle φ\varphi between voltage and current.

pf\displaystyle \text{pf}=PS\displaystyle {}= \frac{P}{S}=cos⁡φ\displaystyle {}= \cos\varphi

Real power PP, in watts, does the work. Reactive power QQ, in var, builds the magnetic field and flows back and forth. Apparent power SS, in volt-amperes (VA), is what the supply and cables must carry. The three form a right triangle.

S2\displaystyle S^2=P2+Q2\displaystyle {}= P^2 + Q^2

For a single-phase load, SS is the voltage times the current. For a balanced three-phase load, use the line-to-line voltage and the line current, with a factor of \(\sqrt{3}\).

S\displaystyle S=3VLIL\displaystyle {}= \sqrt{3}\, V_L I_L

Capacitors supply reactive power on the spot, so less of it travels from the supply. To raise the power factor from pf1\text{pf}_1 to pf2\text{pf}_2 with the same real power, the capacitors must cancel the difference in QQ.

Qc\displaystyle Q_c=P(tan⁡φ1−tan⁡φ2)\displaystyle {}= P\,(\tan\varphi_1 - \tan\varphi_2)
C\displaystyle C=Qc2πfV2\displaystyle {}= \frac{Q_c}{2\pi f V^2}

Here ff is the supply frequency and VV the voltage across the capacitor. In a three-phase bank wired in delta, each of the three capacitors takes a third of QcQ_c with the line voltage across it.

Worked examples

A 230 V motor drawing 10 A at a power factor of 0.8

The supply carries 2,300 VA, but only 1,840 W does work, and 1,380 var swaps back and forth. The phase angle is 36.87°.

At a power factor of 1 the same 1,840 W would need only 8 A. The extra amps still heat the cable, even though they do no work.

Open this example in the tool

Reading a meter that shows 800 W and 1,000 VA

Real over apparent gives a power factor of 0.8. The third side of the triangle is 600 var, at a phase angle of 36.87°.

You need both readings. A meter that shows only watts cannot tell you the power factor, and volts times amps alone gives only the apparent power.

Open this example in the tool

Correcting a 100 kW plant from 0.70 to 0.95

At 0.70 the plant draws 142.9 kVA. Reaching 0.95 takes 69.15 kvar of capacitors, which on a 480 V, 60 Hz delta bank is 265.4 µF per phase. The line current falls from 171.8 to 126.6 A, 26.3% less.

Going on to 0.98 needs 81.7 kvar, and all the way to 1.00 needs 102 kvar, for a current cut of 28.6% and 30%. Each step closer to 1 buys less current for more capacitors.

Open this example in the tool

Reading your result

A power factor runs from 0 to 1. At 1, voltage and current are in step and every amp does work, as in a heater. Motors, transformers and high-intensity discharge lighting pull it down, because their magnetizing current adds reactive power.

Why it costs money. Low power factor means more current for the same work. That means more heating in cables and less spare capacity. The DOE fact sheet says many utilities charge an additional fee below 0.95. Check your own tariff for the line it uses.

Light loads read worse. A motor running far below its rating has a lower power factor than its nameplate says. The DOE sheet lists cutting idling and lightly loaded motors as one of the fixes.

Inductors and capacitors use no real power. On average they take none, so adding capacitors changes the current and the apparent power, but not the watts the load uses.

Common mistakes

Using phase voltage in the three-phase formula. 3VI\sqrt{3}\, V I needs the line-to-line voltage, such as 480 V, not the 277 V from line to neutral.

Sizing capacitors on kVA instead of kW. The kvar formula starts from real power. Use the watts the load draws, not its apparent power.

Expecting capacitors to cut the watts. They lower the current and the kVA. The motor still needs the same real power, so a bill based on kWh alone barely moves.

Ordering the µF without the connection. The same kvar needs a different capacitance in a delta bank, a star bank or a single-phase unit, because the voltage across each capacitor differs.

Questions people ask

Start from the kvar: real power times the change in tan φ between the power factor now and the target. The capacitance then depends on the voltage, frequency and wiring. A 1 kW single-phase load at 0.8, corrected to 1 on 230 V and 50 Hz, needs 750 var, or 45.1 µF.

Sources