Find the log mean temperature difference that drives heat across an exchanger.

Before you rely on this result. This is a planning estimate from the U you enter. A real exchanger design also needs fouling, pressure drop and code checks by a qualified engineer. Sources used on this page.

How it's worked out

In a heat exchanger the gap between the hot and cold fluid is not the same everywhere. It is wide at one end and narrow at the other. The log mean temperature difference, or LMTD, is the one gap that gives the right heat flow when you put it into the rate equation.

ΔTlm\displaystyle \Delta T_{\text{lm}}=ΔT1−ΔT2ln⁡(ΔT1ΔT2)\displaystyle {}= \frac{\Delta T_1 - \Delta T_2}{\ln\left(\frac{\Delta T_1}{\Delta T_2}\right)}

ΔT1\Delta T_1 and ΔT2\Delta T_2 are the gaps at the two ends. Which temperatures pair up depends on the flow. In counterflow the fluids run in opposite directions, so the hot inlet meets the cold outlet.

ΔT1\displaystyle \Delta T_1=Th,in−Tc,out\displaystyle {}= T_{h,\text{in}} - T_{c,\text{out}}
ΔT2\displaystyle \Delta T_2=Th,out−Tc,in\displaystyle {}= T_{h,\text{out}} - T_{c,\text{in}}

In parallel flow both fluids enter at the same end, so the two inlets pair up, then the two outlets.

ΔT1\displaystyle \Delta T_1=Th,in−Tc,in\displaystyle {}= T_{h,\text{in}} - T_{c,\text{in}}
ΔT2\displaystyle \Delta T_2=Th,out−Tc,out\displaystyle {}= T_{h,\text{out}} - T_{c,\text{out}}

The heat flow, or duty QQ, then follows from the heat transfer coefficient UU, which lumps the wall and the film on each side into one figure, and the area AA. Solve the same line for whichever one you do not know.

Q\displaystyle Q=UAFΔTlm\displaystyle {}= U A F \, \Delta T_{\text{lm}}

FF is a correction factor. It is 1 for pure counterflow and parallel flow. A shell-and-tube exchanger with one shell pass and two or more tube passes mixes the two patterns, so its FF is below 1. It is worked out from two ratios of the end temperatures, using the closed form of Bowman, Mueller and Nagle.

R\displaystyle R=Th,in−Th,outTc,out−Tc,in\displaystyle {}= \frac{T_{h,\text{in}} - T_{h,\text{out}}}{T_{c,\text{out}} - T_{c,\text{in}}}
P\displaystyle P=Tc,out−Tc,inTh,in−Tc,in\displaystyle {}= \frac{T_{c,\text{out}} - T_{c,\text{in}}}{T_{h,\text{in}} - T_{c,\text{in}}}

The log comes from adding up the heat flow along the length when U and the heat capacity of each stream stay the same. If a fluid changes a lot in viscosity or boils part way, split the exchanger into zones and work each one.

Worked examples

Priya sizes an oil cooler for 300 kW

Oil cools from 150 to 90 °C while water warms from 30 to 80 °C, in counterflow. The end gaps are 70 and 60 K, so the LMTD is 64.87 K. With U = 500 W/(m²·K) and 300 kW to move, Priya needs 9.25 m² of surface.

The same four temperatures in parallel flow give gaps of 120 and 10 K and an LMTD of only 44.27 K. That needs 13.6 m², 47% more, because the gap collapses at the outlet end.

Open this example in the tool

A shell-and-tube water heater with 25 m² of tubes

A hot stream drops from 180 to 120 °C and heats water from 20 to 70 °C, with one shell pass and two tube passes. R = 1.2 and P = 0.313, which give F = 0.953.

The LMTD is 104.9 K, so the working gap is 99.97 K. With U = 850 W/(m²·K) and 25 m², the exchanger moves 2,124 kW. Pure counterflow on the same tubes would move 2,230 kW.

Open this example in the tool

A cooler whose cold outlet passes its hot outlet

Here the water leaves at 70 °C, hotter than the oil leaves at 60 °C. That is a temperature cross, and one shell copes badly with it: F = 0.658, under the 0.75 floor.

If the unit has 20 m² and is measured moving 450 kW, its U in service works out to 763 W/(m²·K). Read as two shells in series, F rises to 0.934 and the same duty implies U = 537 W/(m²·K). The arrangement you assume changes the U you report.

Open this example in the tool

Reading your result

The LMTD is a difference, not a temperature. A difference of 1 K is the same as 1 °C, and 1.8 °F. That is why the answer reads in K whether you type in °C or K.

It always sits between the two end gaps, and below their plain average. For Priya's cooler the average is 65 K against 64.87 K, close because the gaps are similar. In parallel flow the gaps are 120 and 10 K, and the average of 65 K is far above the log mean of 44.27 K.

Reading F. A design lecture by Daniel Lewin puts it plainly: aim for 0.85 or more, and treat anything below 0.75 as unacceptable. When F drops that low, the usual fix is more shell passes in series. When one fluid condenses or boils at a steady temperature, F is 1 whatever the layout.

Effectiveness is the heat moved over the most that could be moved, set by the stream with the smaller heat capacity rate. It equals the larger of the two temperature changes over the gap between the two inlets.

Common mistakes

Pairing the wrong ends. In counterflow, subtract the cold outlet from the hot inlet. Pairing the inlets, as for parallel flow, gives a different and wrong answer.

Using the counterflow LMTD for a multipass shell without F. That overstates the driving force and undersizes the area by the factor F.

Converting a difference like a temperature. A gap of 20 °C is 20 K, not 293 K. In °F it is 36 °F, with no offset.

Sizing on a clean U. Deposits build up and lower U over time. Use the U your design code or vendor gives with its fouling allowance, not a clean lab figure.

Questions people ask

The gap shrinks along the exchanger in an exponential curve, not a straight line, and the log mean is the true average of that curve. The plain average is always higher, so it would undersize the area. With gaps of 120 and 10 K the average is 65 K but the LMTD is 44.27 K.